Free Electrical Machines MCQs with Answers
1,061 Electrical Machines MCQs from Electrical Engineering, each with the correct answer and a written explanation of why it is correct. Free and unlimited, with no account needed.
Last updated
1,061 questions · page 50 of 54
- A. poor insulation
- B. Overload
- C. loose connections
- D. Core saturation
Explanation: A saturated core draws a nonsinusoidal magnetizing current, and nonsinusoidal current contains harmonics.
Correct answer: Core saturation- A. low power factor wattmeter
- B. unity power factor wattmeter
- C. frequency meter
- D. any type of wattmeter
Explanation: In the open-circuit test, the wattmeter reading is mainly the iron loss, while the power factor is very low because the exciting current…
Correct answer: low power factor wattmeter- A. Core loss
- B. Friction loss
- C. Eddy current loss
- D. Hysteresis loss
Explanation: A transformer has no rotating mechanical parts, so it has no friction loss even at full load.
Correct answer: Friction loss- A. capacitive only
- B. inductive only
- C. inductive or resistive
- D. none of the above
Explanation: A leading, usually capacitive, load can make the reactive voltage-drop component oppose the resistive drop, producing negative regulation.
Correct answer: capacitive only- A. low voltage side of high kVA transformers
- B. high frequency transformers
- C. high voltage side of small capacity transformers
- D. high voltage side of high kVA rating transformers
Explanation: Helical windings are suited to low-voltage, high-current windings because their construction provides good mechanical strength and…
Correct answer: low voltage side of high kVA transformers- A. Core insulation voltage test
- B. Impedance test
- C. Radio interference test
- D. Polarity test
Explanation: Radio interference testing is generally a special test performed when specified, not part of the standard routine tests applied to every…
Correct answer: Radio interference test- A. leading power factor
- B. lagging power factor
- C. unity power factor
- D. zero power factor
Explanation: The resistive voltage drop and reactive voltage drop can cancel when the load power factor is leading, giving zero regulation.
Correct answer: leading power factor- A. value of transformation ratio remains constant
- B. permeability of transformer core remains constant
- C. core flux remains practically constant
- D. primary voltage remains constant
- E. secondary voltage remains constant
Explanation: With rated voltage and frequency held constant, the core flux is approximately constant from no load to full load.
Correct answer: core flux remains practically constant- A. flux density remains unaffected
- B. iron losses are reduced
- C. core flux density is reduced
- D. core flux density is increased
Explanation: Transformer flux is approximately proportional to voltage divided by frequency.
Correct answer: core flux density is increased- A. Low hysteresis loss
- B. High permeability
- C. High thermal conductivity
- D. Adequate mechanical strength
Explanation: Low hysteresis loss, high permeability, and adequate mechanical strength are important core-material properties.
Correct answer: High thermal conductivity- A. load current
- B. load current and voltage
- C. load current, voltage and frequency
- D. load current, voltage, frequency and power factor
Explanation: Load current produces the ampere-turns that establish leakage flux, so leakage flux increases approximately with load current.
Correct answer: load current- A. no losses and magnetic leakage
- B. interleaved primary and secondary windings
- C. a common core for its primary and secondary windings
- D. core of stainless steel and winding of pure copper metal
- E. none of the above
Explanation: An ideal transformer assumes zero winding and core losses, infinite permeability, and no leakage flux.
Correct answer: no losses and magnetic leakage- A. Frequency
- B. Voltage
- C. Current
- D. Any of the above
Explanation: An ordinary transformer changes voltage and current according to its turns ratio, but it does not change the supply frequency.
Correct answer: Frequency- A. Conservator
- B. Breather
- C. Bushings
- D. Buchholz relay
Explanation: The conservator provides space for transformer oil to expand and contract as its temperature changes.
Correct answer: Conservator- A. small air gap
- B. large leakage flux
- C. laminated silicon steel core
- D. fewer rotating parts
Explanation: A transformer core has a very small air gap and high permeability, so only a small magnetising current is needed to establish the flux.
Correct answer: small air gap- A. electrical fault inside the transformer itself
- B. electrical fault outside the transformer in outgoing feeder
- C. for both outside and inside faults
- D. none of the above
Explanation: A Buchholz relay is installed in the oil pipe between the transformer tank and conservator, so it detects gas formation and oil surges…
Correct answer: electrical fault inside the transformer itself- A. short-circuiting of the secondaries
- B. power factor of one of the transformers is leading while that of the other lagging
- C. transformers having higher copper losses will have negligible core losses
- D. loading of the transformers not in proportion to their kVA ratings
Explanation: When parallel transformers have unequal percentage impedances, the lower-impedance transformer takes a greater share of the load.
Correct answer: loading of the transformers not in proportion to their kVA ratings- A. the current on secondary side is negligible
- B. the voltage on secondary side does not vary
- C. the voltage applied on primary side is low
- D. full-load current is not supplied to the transformer
Explanation: In the short-circuit test, only a small primary voltage is needed to circulate rated current because the winding impedance is low.
Correct answer: the voltage applied on primary side is low999. Which of the following is the main advantage of an auto-transformer over a two winding transformer?
- A. Hysteresis losses are reduced
- B. Saving in winding material
- C. Copper losses are negligible
- D. Eddy losses are totally eliminated
Explanation: An autotransformer uses part of the same winding for both primary and secondary, so less copper and conductor material are required than…
Correct answer: Saving in winding material- A. no-load
- B. half-load
- C. near full-load
- D. 10% overload
Explanation: Power transformers operate near full load for much of their service, so they are designed for maximum efficiency near full-load…
Correct answer: near full-load