  • A. Total m.m.f. required
  • B. The number of turns in the exciting winding
  • C. The way in which the winding is distributed
  • D. All of the above

Explanation: Magnetizing current follows approximately from I = MMF/N, so it depends on the required total MMF and the number and distribution of…

Correct answer: All of the above
  • A. One sided axial ventilation
  • B. Two sided axial ventilation
  • C. Multiple inlet system
  • D. All of the above

Explanation: Air-cooled turbo-alternators may use one-sided axial ventilation, two-sided axial ventilation, or multiple-inlet ventilation depending on…

Correct answer: All of the above
  • A. The current in the slot conductors is uniformly distributed over their cross-section
  • B. The leakage path is straight across the slot and around the iron at the bottom
  • C. The permanence of air paths is only considered. The reluctance of iron paths is assumed as zero
  • D. All of the above

Explanation: Slot-leakage calculations assume uniformly distributed slot current, a simplified straight leakage path, and negligible iron reluctance so…

Correct answer: All of the above
  • A. Equivalent power method
  • B. Equivalent current method
  • C. Method of average losses
  • D. Equivalent torque method

Explanation: The method of average losses uses the mean loss over the duty cycle and does not directly account for the peak temperature rise…

Correct answer: Method of average losses
  • A. heating time constant
  • B. cooling time constant
  • C. either A. or B.
  • D. none of the above

Explanation: For exponential heating, the temperature reaches 1 − e⁻¹ = 0.632 of its final value after one heating time constant.

Correct answer: heating time constant
  • A. 200 MW
  • B. 300 MW
  • C. 400 MW
  • D. 600 MW

Explanation: Direct water cooling removes heat very effectively from the conductors, allowing large turbo-generators to reach ratings of roughly 600…

Correct answer: 600 MW
  • A. 2 to 3 times greater
  • B. 3 to 4 times greater
  • C. 4 to 5 times greater
  • D. none of the above

Explanation: In a self-cooled motor, the fan or rotating parts provide much less airflow when the motor is stopped, so cooling is slower at standstill.

Correct answer: 2 to 3 times greater
  • A. no mechanical difficulties
  • B. lesser mechanical difficulties
  • C. greater mechanical difficulties
  • D. none of the above

Explanation: Water passing through a rotating rotor winding requires reliable insulation, seals, joints and rotating connections, creating greater…

Correct answer: greater mechanical difficulties
  • A. solid
  • B. hollow
  • C. perforated
  • D. any ofthe above

Explanation: In direct hydrogen cooling, hydrogen must flow through the conductors to remove heat from the winding interior, so both stator and rotor…

Correct answer: hollow
  • A. "supercharged"
  • B. "inner cooled"
  • C. "conductor cooled"
  • D. any of the above

Explanation: Direct cooling carries the coolant directly through or along the conductors, so such machines are described as supercharged, inner-cooled…

Correct answer: any of the above
  • A. 0.07
  • B. 1.5
  • C. 2.5
  • D. 3.5

Explanation: Hydrogen has a relative density of approximately 0.07 compared with air, making it much lighter.

Correct answer: 0.07
  • A. Increase in efficiency
  • B. Increase in ratings
  • C. Increase in life
  • D. Smaller size of coolers
  • E. All of the above

Explanation: Hydrogen cooling reduces windage loss, improves heat transfer and permits a more compact cooler, thereby increasing efficiency and rating…

Correct answer: All of the above
  • A. Conduction
  • B. Convection
  • C. Radiation
  • D. All of the above

Explanation: Heat can leave an electrical machine by conduction through solid parts, convection to the surrounding fluid and radiation from exposed…

Correct answer: All of the above
  • A. air
  • B. hydrogen
  • C. either A. or B.
  • D. none of the above

Explanation: Hydrogen is much less dense than air, so a rotor experiences less windage and produces less aerodynamic noise while rotating in it.

Correct answer: hydrogen
  • A. 2
  • B. 3
  • C. 5
  • D. 7

Explanation: Hydrogen conducts heat about seven times better than air, which makes it effective for removing heat from large turbo-alternators.

Correct answer: 7
  • A. Direct
  • B. Indirect
  • C. Conventional
  • D. Any of the above

Explanation: Direct cooling circulates the cooling medium within or in direct contact with the winding conductors, so heat does not have to cross the…

Correct answer: Direct
  • A. 50 MW
  • B. 100 MW
  • C. 200 MW
  • D. none of the above

Explanation: Conventional hydrogen cooling is suitable for turbo-alternators up to roughly 200 MW per unit.

Correct answer: 200 MW
  • A. 1.5
  • B. 2.5
  • C. 3.5
  • D. 4.5

Explanation: Hydrogen has a heat-transfer coefficient approximately 1.5 times that of air under comparable conditions, allowing it to remove heat more…

Correct answer: 1.5
  • A. 10 MW
  • B. 30 MW
  • C. 60 MW
  • D. 150 MW

Explanation: A multiple-inlet air-cooling arrangement improves the distribution of cooling air and is commonly used for turbo-alternators rated up to…

Correct answer: 60 MW
  • A. conduction
  • B. convection
  • C. radiation
  • D. any ofthe above

Explanation: Air blasts increase the movement of air over the heated surface, thereby increasing forced convection.

Correct answer: convection