- A. 0.555
- B. 0.578
- C. 0.5457
- D. 0.6
Explanation: For superheated steam, using an isentropic exponent of about 1.3 gives a critical pressure ratio near 0.546.
Correct answer: 0.5457- A. 0.6
- B. 0.578
- C. 0.555
- D. 0.5457
Explanation: For initially dry-saturated steam, the critical pressure ratio is approximately 0.577 to 0.578. Therefore, option b is the closest value.
Correct answer: 0.578- A. pvls=C
- B. pv1126 = C
- C. pv1A = C
- D. pv = C
Explanation: Superheated steam behaves approximately like a gas during nozzle expansion, so its isentropic relation is commonly written as p v^1.3 = C.
Correct answer: pvls=C- A. series wound generator
- B. shunt wound generator
- C. synchronous generator
- D. none of the above
Explanation: A booster is normally a series-wound generator connected in series with a feeder to compensate for voltage drop.
Correct answer: series wound generator- A. reactors
- B. generators
- C. transformers
- D. all of the above
Explanation: Electromechanical voltage regulators, such as regulators used with alternators, adjust generator excitation to maintain terminal voltage.
Correct answer: generators- A. using reactors
- B. increasing the load
- C. adjusting the governor
- D. reducing the terminal voltage
- E. none of the above
Explanation: Generator frequency follows f = PN/120, so it increases when rotor speed is increased.
Correct answer: adjusting the governor- A. Its secondary current is 5 A
- B. Its secondary voltage is 400 V
- C. Its rating is 2 kVA
- D. Its secondary current is 20 A
- E. It is a step-up transformer
Explanation: For an ideal transformer, V₂/V₁ = N₂/N₁ = 2, so V₂ = 400 V, while current changes inversely to 5 A.
Correct answer: Its secondary current is 20 A- A. hysteresis and eddy current losses
- B. friction and windage losses
- C. copper losses
- D. none of the above
Explanation: At fixed applied voltage and frequency, hysteresis and eddy-current losses depend mainly on the core flux and remain nearly constant as…
Correct answer: hysteresis and eddy current losses1409. Losses which occur in rotating electric machines and do not occur in transformers are___________?
- A. friction and windage losses
- B. magnetic losses
- C. hysteresis and eddy current losses
- D. copper losses
Explanation: Friction and windage losses require moving mechanical parts, so they occur in rotating machines but not in a stationary transformer.
Correct answer: friction and windage losses- A. eddy current loss will decrease
- B. eddy current loss will increase
- C. eddy current loss will remain unchanged
- D. none of the above
Explanation: With applied voltage fixed, core flux is approximately proportional to 1/frequency.
Correct answer: eddy current loss will remain unchanged1411. In a power or distribution transformer about 10 per cent end turns are heavily insulated__________?
- A. to withstand the high voltage drop due to line surge produced by the shunting capacitance of the end turns
- B. to absorb the line surge voltage and save the winding of transformer from damage
- C. to reflect the line surge and save the winding of a transformer from damage
- D. none of the above
Explanation: A line surge produces a nonuniform voltage distribution in the end turns because of the winding's shunt capacitance, placing excessive…
Correct answer: to withstand the high voltage drop due to line surge produced by the shunting capacitance of the end turns- A. core built-up of laminations of cold rolled grain oriented steel
- B. core built-up of laminations of hot rolled sheet
- C. either of the above
- D. none of the above
Explanation: Cold-rolled grain-oriented steel provides high permeability along the grain direction and lower hysteresis and eddy-current losses than…
Correct answer: core built-up of laminations of cold rolled grain oriented steel- A. zoom
- B. hum
- C. ringing
- D. buzz
Explanation: The familiar low-frequency noise of a transformer is called hum, mainly caused by magnetostriction and the resulting vibration of the core…
Correct answer: hum- A. Bushings
- B. Core
- C. Primary winding
- D. Secondary winding
Explanation: Bushings pass the transformer conductors safely through the earthed tank and are mounted externally, so they can be seen from outside.
Correct answer: Bushings- A. Cellulose
- B. Asbestos
- C. Mica
- D. Glass fibre
Explanation: Mica has excellent dielectric strength and a very high temperature capability, commonly associated with Class C insulation.
Correct answer: Mica- A. short-circuit test
- B. back-to-back test
- C. open circuit test
- D. any of the above
Explanation: The back-to-back, or Sumpner, test uses two identical transformers to reproduce full-load conditions while measuring losses, temperature…
Correct answer: back-to-back test- A. Horn gaps
- B. Thermal overload relays
- C. Breather
- D. Conservator
Explanation: Horn gaps provide a low-resistance path for lightning and switching surges, diverting them safely to earth.
Correct answer: Horn gaps- A. A good voltage regulation of a transformer means
- B. output voltage fluctuation from no load to full load is least
- C. output voltage fluctuation with power factor is least
- D. difference between primary and secondary voltage is least
- E. difference between primary and secondary voltage is maximum
Explanation: Good voltage regulation means the secondary-terminal voltage changes very little between no-load and full-load conditions.
Correct answer: output voltage fluctuation from no load to full load is least- A. 0.8 leading power factor
- B. 0.8 lagging power factor
- C. zero power factor
- D. unity power factor
Explanation: With load current fixed, transformer losses are essentially fixed, while useful output is proportional to power factor.
Correct answer: unity power factor- A. on full-load
- B. on overload
- C. on leading power factor
- D. on zero power factor
Explanation: At a leading power factor, the voltage drop caused by transformer leakage reactance can be offset by the resistive drop, bringing…
Correct answer: on leading power factor