Free Process Control and Instrumentation MCQs with Answers
254 Process Control and Instrumentation MCQs from Chemical Engineering, each with the correct answer and a written explanation of why it is correct. Free and unlimited, with no account needed.
Last updated
254 questions · page 6 of 13
- A. Polarimeter
- B. CO2 analyser
- C. Spectrometer
- D. Chromatograph
Explanation: A thermal-conductivity gas analyser infers composition from the change in heat conduction of the gas mixture, and it is commonly used for…
Correct answer: CO2 analyser- A. Radiation pyrometer
- B. Optical pyrometer
- C. Resistance pyrometer
- D. Infra red pyrometer
Explanation: A resistance pyrometer is a contact instrument because its sensing element must be placed in contact with the body whose temperature is…
Correct answer: Resistance pyrometer- A. Mercury in glass thermometer with covering
- B. None of these
- C. Pressure gauge with one bellow, two tubes and a tank
- D. Bare mercury in glass thermometer
Explanation: A bare mercury-in-glass thermometer is normally treated as a first-order instrument, since its bulb temperature follows the surroundings…
Correct answer: Bare mercury in glass thermometer- A. Very high pressure
- B. High vacuum
- C. Liquid level under pressure
- D. Liquid level at atmospheric pressure
Explanation: A Pirani gauge measures very low pressures by relating the heat loss from a heated filament to the gas pressure, so it is used for…
Correct answer: High vacuum- A. Humidity of air
- B. % CO2 in flue gas
- C. % O2 in flue gas
- D. Speed of a submarine
Explanation: A zirconia probe develops an electrochemical voltage related to the difference in oxygen partial pressure, so it is used to determine…
Correct answer: % O2 in flue gas- A. Vapor pressure
- B. Constant volume gas
- C. Mercury in glass
- D. Bimetallic
Explanation: A mercury-in-glass thermometer works because mercury expands in volume when heated and rises through a calibrated capillary.
Correct answer: Mercury in glass- A. Transportation lag
- B. None of these
- C. Second order system
- D. First order system
Explanation: For a first-order system, the sinusoidal amplitude ratio is 1 divided by the square root of 1 plus the squared frequency time constant, so…
Correct answer: First order system- A. Mcleod
- B. Pirani
- C. Ionisation
- D. None of these
Explanation: A pressure of 0.01 psi absolute is about 0.52 mmHg, which lies in the low-pressure range commonly measured by a McLeod gauge.
Correct answer: Mcleod- A. Melting
- B. Both A. & B.
- C. Boiling
- D. Neither A. nor B.
Explanation: Temperature instruments are commonly calibrated against reproducible fixed points such as the melting or freezing point and the boiling…
Correct answer: Both A. & B.- A. Sling psychrometer
- B. Hair-hygrometer
- C. Weighing
- D. High resistance Wheatstone bridge circuit
Explanation: In continuous paper-moisture measurement, water changes the electrical resistance of the paper, and a high-resistance Wheatstone bridge…
Correct answer: High resistance Wheatstone bridge circuit- A. CO2 percentage in the flue gas
- B. Specific gravity of petrofuels
- C. Composition of an alloy
- D. O2 percentage in the flue gas
Explanation: Carbon dioxide has a thermal conductivity sufficiently different from the major gases in flue gas for a thermal-conductivity analyser to…
Correct answer: CO2 percentage in the flue gas- A. Electronic
- B. Pneumatic
- C. Hydraulic
- D. None of these
Explanation: A flapper-nozzle arrangement converts a mechanical displacement into a pneumatic pressure signal, forming the basic transmitter or…
Correct answer: Pneumatic- A. Dead zone
- B. Drift
- C. Static error
- D. None of these
Explanation: Static error is the difference between the true value and the value indicated by an instrument under steady conditions, so it directly…
Correct answer: Static error- A. P
- B. PD
- C. PID
- D. PI
Explanation: A PI controller generally has the longest settling or stabilising time because integral action removes offset but can make the response…
Correct answer: PI- A. Optical pyrometer
- B. Mercury in glass thermometer
- C. Iron-constantan thermocouple
- D. Alcohol filled thermometer
Explanation: An optical pyrometer estimates temperature from thermal radiation and is generally less accurate than direct-contact thermometers over…
Correct answer: Optical pyrometer- A. High drift
- B. High fidelity
- C. High measuring lag
- D. Poor reproducibility
Explanation: High fidelity means an instrument reproduces the input signal accurately in magnitude and form, making it a desirable characteristic.
Correct answer: High fidelity- A. Under damped
- B. None of the above
- C. Over damped
- D. Critically damped
Explanation: Two identical non-interacting tanks in series give a denominator proportional to (τs + 1)², which has two equal real poles.
Correct answer: Critically damped- A. 1/(s2 + 2)
- B. 1/(s2 - 2s + 3)
- C. 1/(s2 + 2s + 2)
- D. exp (-20s)/(s2 + 2s - 1)
Explanation: A system is stable when all poles lie in the left half of the s-plane. For option c, s² + 2s + 2 = 0 gives poles -1 ± j, whereas the other…
Correct answer: 1/(s2 + 2s + 2)- A. Determining water purity
- B. Solids and metal analysis
- C. Determination of CO2 in gases
- D. NOx determination
Explanation: Emission spectroscopy identifies elements from the characteristic wavelengths emitted by excited atoms, so it is widely used for elemental…
Correct answer: Solids and metal analysis- A. 800
- B. 400
- C. 1200
- D. 1500
Explanation: Optical radiation pyrometers are used for high-temperature measurement and typically begin operating at about 800°C.
Correct answer: 800